The Basics of Evaporative Cooling

Contents
Summary
What is evaporative cooling?
What's so great about evaporative cooling?
What kind of temperature reduction can I expect with evaporative cooling?
Where can I use evaporative cooling?
How much tonnage can I save using supplementary indirect/indirect evaporative cooling?
Appendix A: Psychrometric chart 101


Summary
Evaporative cooling has made summers more bearable for thousands of years and with 21st century technology provides effective, economical, environmentally friendly, and healthy cooling. Evaporative cooling comes in five flavors: direct, indirect, indirect/direct, indirect/indirect, and indirect DX. Evaporative cooling works well in the Pacific Northwest, alone or as a supplement to a chiller or DX system.

What is evaporative cooling?
Evaporative cooling is responsible for the chill you feel when a breeze strikes your skin—the air evaporates the water on your skin, with your body heat providing the energy. The ancient Egyptians hung wet mats in their doors and windows, and wind blowing through the mats cooled the air—the first attempt at air conditioning. This basic idea was refined through the centuries: mechanical fans to provide air movement in the 16th century, cooling towers with fans that blew water-cooled air inside factories in the early 19th century, swamp coolers in the 20th century.

These simple examples illustrate direct evaporative cooling. Modern technology has dramatically increased the efficiency and effectiveness of direct evaporative cooling and made possible four other types of evaporative cooling: indirect evaporative cooling, indirect/direct evaporative cooling, indirect/indirect evaporative cooling, and indirect evaporative cooling with DX back-up.

NOTE
Dry bulb is the sensible air temperature. Wet bulb is the lowest air temperature achievable by evaporating water into the air to bring the air to saturation.

direct evaporative cooling
With direct evaporative cooling, outside air is blown through a water-saturated medium (usually cellulose) and cooled by evaporation. The cooled air is circulated by a blower.

Direct evaporative cooling adds moisture to the air stream until the air stream is close to saturation. The dry bulb temperature is reduced, while the wet bulb temperature stays the same.

indirect evaporative cooling
With indirect evaporative cooling, a secondary (scavenger) air stream is cooled by water. The cooled secondary air stream goes through a heat exchanger, where it cools the primary air stream. The cooled primary air stream is circulated by a blower.

Indirect evaporative cooling does not add moisture to the primary air stream. Both the dry bulb and wet bulb temperatures are reduced.

During the heating season, an indirect system’s heat exchanger can preheat outside air if exhaust air is used as the secondary air stream.

indirect/direct evaporative cooling


With indirect/direct evaporative cooling, the primary air stream is cooled first with indirect evaporative cooling and then cooled further with direct evaporative cooling.
indirect/indirect evaporative cooling


In the first stage of indirect/indirect evaporative cooling, the primary air stream is cooled by indirect evaporative cooling.

In the second stage, the water used in first-stage cooling passes through the wet side of a coil. Additional sensible heat is removed from the primary air stream, and no moisture is added to the primary air.
indirect evaporative cooling/DX
With indirect evaporative cooling with DX back-up, the primary air stream is cooled first with indirect evaporative cooling. Most of the time, this cools the primary air stream to the desired temperature. When more cooling is required, the supplemental DX module cools the air further to reach the desired temperature

This unit is in beta release, and achievable energy savings are still being tested.

What’s so great about evaporative cooling?
Evaporative cooling is economical, effective, environmentally friendly, and healthy.

Economical
Evaporative cooling is economical because it:

  • Reduces DX/chilled water cooling requirements for fresh air.
  • Cuts mechanical cooling costs 25% to 65%.
  • Provides 100% make-up air cooling at half the cost of mechanical equipment cooling.
  • Increases existing equipment cooling capacities without adding mechanical cooling.
  • Increases compressor life.
  • Increases heat exchanger life.

Effective

  • Evaporative cooling actually becomes more effective as the temperature increases—just when DX air conditioning becomes less effective.
  • Evaporative cooling works in all areas of the country, not just in hot, dry climates. Although the Pacific Northwest is certainly damp in winter, it is dry in summer. In fact, humidity in this region of the country almost always decreases proportionally as the temperature increases. So the cooling power of evaporative systems increases as the temperature increases.

Environmentally friendly
Because evaporative cooling does not use chlorofluorocarbons (CFCs), it does not contribute to ozone depletion.

Healthy
Evaporative cooling is healthy and comfortable because it:

  • Brings in outside air and exhausts stale air, smoke, odors, and germs.
  • Helps maintain natural humidity levels, which benefits both people and furniture and cuts static electricity.
  • Does not need an air-tight structure for maximum efficiency, so building occupants can open doors and windows.

What kind of temperature reductions can I expect with evaporative cooling?

The greater the difference between the wet bulb and dry bulb temperatures, the greater the achievable temperature reduction. Here’s how to calculate temperature reductions achievable with direct, indirect, indirect/direct, and indirect/indirect evaporative cooling.

These examples use a starting dry bulb (DB) temperature of 86o and wet bulb (WB) temperature of 66o.

Temperature reduction achievable using direct evaporative cooling

NOTE
With direct evaporative cooling, the dry bulb temperature is reduced while the web bulb temperature remains the same.

  1. Temp drop achievable = (dry bulb - wet bulb ) x (efficiency* of the media)
    Example: (86o - 66o) x .9 = 18o

  2. Achievable temp = dry bulb - temp drop achievable
    Example: 86o - 18o = 68o DB/66o WB**

  3. Starting DB: 86o
    Ending DB: 68o

*Efficiency is usually 90%
**Because cooling is achieved by adding moisture to the supply air stream, the new dry bulb/web bulb temperatures are found on the web bulb gradient.

NOTE
Refer to Appendix A for more information on using psychrometric charts to calculate temperature reduction using evaporative cooling.

Temperature reduction achievable using indirect evaporative cooling

NOTE
With indirect evaporative cooling, both the dry bulb and web bulb temperatures are reduced.

  1. Temp drop achievable = (dry bulb – wet bulb) x (efficiency* of indirect module)
    Example: (86o - 66o) x .7 = 14o

  2. Achievable temp = dry bulb – temp drop achievable
    Example: 86o – 14o = 72o DB/61.4o WB**

  3. Starting DB: 86o
    Ending DB: 72o

*Efficiency is usually 60%-70%
**Because no moisture is added to the supply air stream, the new dry bulb/wet bulb temperatures are found on the dry bulb gradient.

Temperature reduction achievable using indirect/direct evaporative cooling

First calculate the dry bulb and wet bulb temperatures achievable with indirect evaporative cooling:

  1. Temp drop achievable = (dry bulb - wet bulb ) x (efficiency of indirect module) Example: (86o - 66o) x .7 = 14o

  2. Achievable temp = dry bulb - temp drop achievable
    Example: 86o - 14o = 72o DB/61.4o WB

  3. Starting DB: 86o
    Ending DB: 72o

Then use the dry bulb/wet bulb values from step 3 to calculate the dry bulb/wet bulb temperatures achievable with direct evaporative cooling:

  1. Temp drop achievable: (dry bulb - wet bulb ) x (efficiency of the media )
    Example: (72o - 61.4o) x .9 = 9.5o

  2. Achievable temp = dry bulb - temp drop achievable
    Example: 72o - 9.5o = 62.5o DB/61.4o WB

  3. Total temperature reduction using indirect/direct evaporative cooling:
    Starting DB: 86o
    Ending DB: 62.5o

Temperature reduction achievable using indirect/indirect evaporative cooling

First calculate the dry bulb and wet bulb temperatures achievable with the first stage of indirect evaporative cooling:

  1. Temp drop achievable = (dry bulb - wet bulb ) x (efficiency of indirect module) Example: (86o - 66o) x .7 = 14o

  2. Achievable temp = dry bulb - temp drop achievable
    Example: 86o - 14o = 72o DB/61.4o WB

  3. Starting DB: 86o
    Ending DB: 72o

Then use the dry bulb/wet bulb values from step 3 to calculate the dry bulb/wet bulb temperatures achievable with the second stage of indirect evaporative cooling, assuming 50% effectiveness:

  1. Temp drop achievable: (dry bulb - wet bulb ) x (efficiency of the media )
    Example: (72o - 61.4o) x .5 = 5.3o

  2. Achievable temp = dry bulb - temp drop achievable
    Example: 72o - 5.3o = 66.7o DB/59.5o WB

  3. Total temperature reduction using indirect/indirect evaporative cooling:
    Starting DB: 86o
    Ending DB: 66.7o

Where can I use evaporative cooling?
In many locations and for many applications, evaporative cooling is all the cooling required to maintain a comfortable indoor environment. In hotter areas or where cooling loads are high, such as in office buildings, one of the most useful applications for indirect evaporative cooling is supplementing a chiller or DX system. By cooling the air stream before it reaches the cooling coil, an indirect evaporative unit extends chiller life, cuts energy costs, and provides the boost the chiller needs to function effectively on hot days. You can add an indirect evaporative cooling unit to an existing system or design a new cooling system that incorporates the indirect unit with the chiller or a standard roof-top DX system.

How much tonnage can I save using supplementary indirect/indirect evaporative cooling?

Example conditions
Required outside air volume: 10,000 CFM
Required refrigeration tonnage to meet building cooling load: 25 tons

Formula
Tons saved = [1.08][1% Design delta T][efficiency][CFM]/12,000

Examples
Oregon
Portland: [1.08][86-66][.90][10,000]/12,000 = 16.2 tons saved
Bend: [1.08][89-61][.90][10,000]/12,000 = 22.7 tons saved
Medford: [1.08][95-66][.90][10,000]/12,000 = 23.49 tons saved

Washington
Seattle: [1.08][81-64][.90][10,000]/12,000 = 13.8 tons saved
Spokane: [1.08][89-61][.90][10,000]/12,000 = 22.7 tons saved
WallaWalla: 1.08[[[95-65][.90][10,000]/12,000 = 24.3 tons saved

Idaho
Boise: [1.08][94-63][.90][10,000]/12,000 = 25.11 tons saved
Idaho Falls: [1.08][89-60][.90][10,000]/12,000 = 23.49 tons saved
Pocatello: [1.08][90-60][.90][10,000]/12,000 = 24.3 tons saved

Approximate costs for indirect and indirect/indirect evaporative modules
Indirect evaporative module: $1.95 to $2.30 per CFM
Indirect/direct evaporative module: $3.25 to $3.50 per CFM
Indirect/indirect evaporative module: $4.00 to $5.00 per CFM


Appendix A: Psychrometric chart 101

Psychrometry is the study of moist air and the changes in its conditions. The psychrometric chart graphically represents the relationship between air temperature and moisture content and is a basic design tool for mechanical engineers and designers.

You can represent psychrometric processes (that is, any changes in the condition of the atmosphere) on the psychrometric chart. Common processes include:

  • Sensible cooling/sensible heating
  • Cooling and dehumidification/heating and humidification
  • Humidification/dehumidification
  • Evaporative cooling/chemical dehydration

Figure 1 shows a basic psychrometric chart.

Figure 1 Psychrometric chart

The following sections explain using a psychrometric chart to calculate how much you can reduce dry bulb temperature using direct, indirect, indirect/direct, and indirect/indirect evaporative cooling.

Using a psychrometric chart to calculate the dry bulb temperature possible with direct evaporative cooling

NOTE
With direct evaporative cooling, the dry bulb temperature is reduced while the web bulb temperature remains constant.

  1. Start with the dry bulb (DB) and wet bulb (WB) design conditions for the location you are interested in. For example, Portland’s 1% design conditions are 86o DB/66o WB F.

    NOTE
    The ASHRAE handbook Fundamentals contains design conditions.

  2. Find where 86o on the dry bulb line intersects with 66o on the wet bulb line (see Figure 2). That is the starting point.

    Figure 2 Starting point

  3. Calculate the temperature drop achievable using the following formulas. Figure 3 graphically represents the process.

    Temperature drop achievable = (dry bulb - wet bulb ) x (efficiency of the media)
    Example: (86o - 66o) x .9 = 18o

    Achievable temperature = dry bulb - temp drop achievable
    Example: 86o - 18o = 68o DB

    NOTE
    Because cooling is achieved by adding moisture to the supply air stream, the new dry bulb/wet bulb temperatures are found on the wet bulb gradient.


    Figure 3 Direct evaporative cooling

  4. Starting temperatures : 86o DB/66o WB
    Ending temperatures: 68o DB/66o WB

Using a psychrometric chart to calculate the dry bulb temperature possible with indirect evaporative cooling

NOTE
With indirect evaporative cooling, both the dry bulb and web bulb temperatures are reduced.

  1. Start with the dry bulb (DB) and wet bulb (WB) design conditions for the location you are interested in. For example, Portland’s 1% design conditions are 86o DB/66o WB F.

  2. Find where 86o on the dry bulb line intersects with 66o on the wet bulb line (see Figure 2 in the previous section). That is the starting point.

  3. The efficiency of the indirect module determines the percentage of the possible temperature drop you can achieve with indirect evaporative cooling. Efficiency of the indirect module is usually 60% to 70%.

    Calculate the new dry bulb temperature using the following formulas. Figure 4 graphically represents the process.

    Temp drop achievable = (dry bulb – wet bulb) x (efficiency of indirect module)
    Example: (86o - 66o) x .7 = 14o

    Achievable temperature = dry bulb – temp drop
    Example: 86o – 14o = 72o DB

    NOTE
    Because no moisture is added to the supply air stream, the new dry bulb/wet bulb temperatures are found on the dry bulb gradient.


    Figure 4 Indirect evaporative cooling: new dry bulb temperature

  4. Indirect evaporative cooling decreases the wet bulb temperature as well as the dry bulb temperature. Figure 5 shows how to use the psychrometric chart to calculate the new wet bulb temperature.

    NOTE
    Because no moisture is added to the supply air stream, the new dry bulb/wet bulb temperatures are found on the dry bulb gradient.


    Figure 5 Indirect evaporative cooling: new wet bulb temperature

  5. Starting temperatures : 86o DB/66o WB
    Ending temperatures: 72o DB/61.4o WB

Using a psychrometric chart to calculate the dry bulb temperature possible with indirect/direct evaporative cooling

First calculate the dry bulb and wet bulb temperatures achievable with indirect evaporative cooling:

  1. With starting temperatures of 86o DB/ 66o WB, the achievable temperature using indirect evaporative cooling is 72o DB/61.4o WB (refer to the previous section).

Then use the dry bulb/wet bulb values from step 1 to calculate the dry bulb/wet bulb temperatures achievable with direct evaporative cooling:

  1. After being reduced by indirect evaporative cooling, the new starting point is 72/61.4.

  2. From the new starting point, use the following formulas to calculate the temperature drop achievable with direct evaporative cooling. Figure 6 illustrates the process.

    Temp drop achievable: (dry bulb - wet bulb ) x (efficiency of the media )
    Example: (72o - 61.4o) x .9 = 9.5o

    Achievable temp = dry bulb - temp drop achievable
    Example: 72o - 9.5o = 62.5o DB/61.4o WB

    Figure 6 Indirect/direct evaporative cooling temperature drop achievable

  3. Starting termperatures: 86o DB/66o WB
    Ending temperatures: 62.5o DB/61.4o WB

Using a psychrometric chart to calculate the dry bulb temperature possible with indirect/indirect evaporative cooling

First calculate the dry bulb and wet bulb temperatures achievable with the first stage of indirect evaporative cooling:

  1. With starting temperatures of 86o DB/ 66o WB, the achievable temperature using indirect evaporative cooling is 72o DB/61.4o WB (refer to the section on indirect evaporative cooling). Efficiency of 70% is used for the first indirect stage.

Then use the dry bulb/wet bulb values from step 1 to calculate the dry bulb/wet bulb temperatures achievable with the second stage of indirect evaporative cooling:

  1. After being reduced by indirect evaporative cooling, the new starting point is 72/61.4.

  2. From the new starting point, use the following formulas to calculate the temperature drop achievable with the second stage of indirect evaporative cooling. Efficiency of 50% is used for the second indirect stage. Figure 7 illustrates the process.

    Temp drop achievable: (dry bulb - wet bulb ) x (efficiency of the media )
    Example: (72o - 61.4o) x .5 = 5.3o

    Achievable temp = dry bulb - temp drop achievable
    Example: 72o - 5.3o = 66.7o DB/59.5o WB

    Figure 7 Indirect/indirect evaporative cooling temperature drop achievable

  3. Starting termperatures: 86o DB/66o WB
    Ending temperatures: 66.7o DB/59.5o WB